FEATURES
- Designed for both indoor and outdoor use;
- Equipped with tamper-resistant screws to prevent unauthorized entry.
- Two synchronized switches are enclosed in a durable terminal block. Terminals are easy to read and wire.
- Built-in mechanical time delay feature; minimizing the risk of false alarms due to pressure surges or air trapped in the system.
- Offers excellent performance during riser vibrations caused by large in-rushes of water.
- Designed and built for accuracy and repeatability.
- Sealed retard mechanism immune to dust and other contaminants
- Field-replaceable retard mechanism and SPDT switches
- Rugged, dual SPDT switches enclosed in a durable terminal block
- 100 percent synchronization activates both the alarm panel and local bell
- Tamper-resistant cover screws
TECHNICAL DATA
FLOW SENSITIVITY RANGE | 4-10 GPM (15-38LPM) | |
CONTACT RATING | Two sets of SPDT 8A@250VAC; 3A@24VDC; 2.5A@ 30VDC. | |
WORKING PRESSURE | 450PSI. | |
WORKING TEMPERATURE | 0°C to 68°C | |
CORROSION PROTECTION | Fusion Bonded Epoxy Coated Interior and Exterior or Enamel Spray Paint, Interior and Exterior | |
WORKING PRESSURE | 450psi. | |
MAXIMUM SURGE | 18 FPS (5.5 m/s) | |
CORROSION PROTECTION | Fusion Bonded Epoxy Coated Interior and Exterior or Enamel Spray Paint, Interior and Exterior. | |
COMPATIBLE PIPE | Steel water pipe, schedule 10 through 40 | |
CONDUIT ENTRANCES | Two openings for ½” conduit. | |
SERVICE USE | • Automatic Sprinkler: NFPA 13 • One or Two Family Dwelling: NFPA 13D Residential • Occupancies up to 4 Stories: NFPA 13R National Fire Alarm • Code: NFPA 72 |